structure
The electric two-way valve consists of two parts: a driver and a valve body. The driver is driven by a synchronous motor and has spring reset and manual valve opening lever control functions.
main technical parameters
Control form: Normally closed type (When the wind disc is not in use and the electric valve is not electrified, the electric valve is closed and the wind disc does not flow through water; after electrified, the driver motor rotates, pushing the valve body core rod to move, opening the valve body, and chilled water circulates.)
Drive motor: hysteresis synchronous motor;
Driver working voltage: 200VAC, 50Hz/60Hz;
Power consumption: ≤5.7VA;
Valve body pressure: 1.6MPa;
Allowable pressure difference: ≤0.12MPa;
Applicable medium temperature: 2℃-95℃;
Applicable ambient temperature: 0℃-60℃ The maximum relative humidity is non-condensation;
Opening and closing time: about 10 seconds on and about 5 seconds off;
Valve stem: 316 round ground stainless steel;
Spring: 316 stainless steel